2.3 TECHNICAL INFORMATION
Power rating
Protect C.1000 1000 VA (cos φ = 0.8 lag.) 800 W
Protect C.2000 2000 VA (cos φ = 0.8 lag.) 1600 W
Protect C.3000 3000 VA (cos φ = 0.8 lag.) 2400 W
UPS Input 1ph~ / N / PE
Rated input voltage 200 / 208 / 220 / 230 / 240 VAC
Rectifier voltage range
(without battery
operation, 100 % load,
cos = 0.8 lag.)
176 – 300 VAC
Rectifier voltage range
(without battery operation,
50 % load, cos = 0.8 lag.)
110 – 300 VAC
Nominal frequency
50 Hz / 60 Hz
(autom. detection or manual)
Frequency tolerance ±10 %
Power consumption at full load (max.)
Protect C.1000 4.8 / 4.6 / 4.4 A
U
N
= 220 / 230 / 240 VAC
Protect C.2000 8.9 / 8.5 / 8.2 A
U
N
= 220 / 230 / 240 VAC
Protect C.3000 13.1 / 12.5 / 12.0 A
U
N
= 220 / 230 / 240 VAC
Bypass voltage range 176 VAC – 264 VAC
Mains feedback factor ≥0.99 (THDi <5 %)
Connection IEC connector
UPS Output
Rated output voltage 200 / 208 / 220 / 230 / 240 VAC ±2 %
Power reduction at 200 VAC 20 % /
at 208 VAC 10 %
Nominal frequency 50 Hz / 60 Hz ±0.2 Hz
(Tolerance in battery mode or free running
in variable-frequency inverter mode)
Synchronization range 50 Hz / 60 Hz ±10 %
Synchronization speed 1 Hz/s